Research article Special Issues

Transients outrush current analysis and mitigation: A Case study of Afghanistan North East power system

  • This study evaluates the inconveniences raised by the installation of Shunt Capacitor Banks (SCB) along the North East Power System (NEPS) in Afghanistan. Besides the numerous advantages, a capacitor bank usually has some drawbacks in terms of transient currents which affect the quality of power supply and exceed the withstand capability of associated equipment. In this study, transient outrush current injects by installed SCB into the nearby faulted point at Pule Khumri and Chimtala substations is investigated. Outrush transient is produced by SCB when the breaker is operating to disconnect the faulted circuit. By applying different methods can mitigate outrush transient and protect the system which Current Limiting Inductance (CLI) is preferred in this study. Integrating CLI in series with SCB is the most relevant method which can limit the amplitude, frequency, and the rate of rise of the outrush transient. The use of inductance could otherwise create some excessive voltage which might exceeds the withstand capability of circuit breakers. Hence sensitivity analysis based on Transient Recovery Voltage (TRV) to confirm the robustness of the proposed approach is carried out. The evaluation is accomplished based on the result derived from the Electromagnetic Transients Program (EMTP), ATP package.

    Citation: Abdul Matin Ibrahimi, K Narayanan, Mohammed Elsayed Lotfy, Mir Sayed Shah Danish, Mikaeel Ahmadi, Tomonobu Senjyu. Transients outrush current analysis and mitigation: A Case study of Afghanistan North East power system[J]. AIMS Energy, 2019, 7(4): 493-506. doi: 10.3934/energy.2019.4.493

    Related Papers:

    [1] Gul Ahmad Ludin, Mohammad Amin Amin, Ahmad Shah Irshad, Soichiro Ueda, Zakirhussain Farhad, M. H. Elkholy, Tomonobu Senjyu . Power transmission in Afghanistan: Challenges, opportunities and proposals. AIMS Energy, 2024, 12(4): 840-871. doi: 10.3934/energy.2024040
    [2] W.A.D.S.S. Weerasinghe, K.P. Vidanapathirana, K.S. Perera . Performance evaluation of polyaniline-based redox capacitors with respect to polymerization current density. AIMS Energy, 2018, 6(4): 593-606. doi: 10.3934/energy.2018.4.593
    [3] Nagaraj C, K Manjunatha Sharma . Fuzzy PI controller for bidirectional power flow applications with harmonic current mitigation under unbalanced scenario. AIMS Energy, 2018, 6(5): 695-709. doi: 10.3934/energy.2018.5.695
    [4] Shafiuzzaman Khan Khadem, Malabika Basu, Michael F. Conlon . Capacity enhancement and flexible operation of unified power quality conditioner in smart and microgrid network. AIMS Energy, 2018, 6(1): 49-69. doi: 10.3934/energy.2018.1.49
    [5] Abdulrahman J. Babqi, NasimUllah, Ahmed Althobaiti, Hend I. Alkhammash, Asier Ibeas . Current model predictive fault-tolerant control for grid-connected photovoltaic system. AIMS Energy, 2022, 10(2): 273-291. doi: 10.3934/energy.2022015
    [6] Rasool M. Imran, Kadhim Hamzah Chalok . Innovative mode selective control and parameterization for charging Li-ion batteries in a PV system. AIMS Energy, 2024, 12(4): 822-839. doi: 10.3934/energy.2024039
    [7] Awatif Nadia, Md. Sanwar Hossain, Md. Mehedi Hasan, Sinthia Afrin, Md Shafiullah, Md. Biplob Hossain, Khondoker Ziaul Islam . Determination of transmission reliability margin for brownout. AIMS Energy, 2021, 9(5): 1009-1026. doi: 10.3934/energy.2021046
    [8] Ahsan Iqbal, Ayesha Ayoub, Asad Waqar, Azhar Ul-Haq, Muhammad Zahid, Syed Haider . Voltage stability enhancement in grid-connected microgrid using enhanced dynamic voltage restorer (EDVR). AIMS Energy, 2021, 9(1): 150-177. doi: 10.3934/energy.2021009
    [9] Giovanni Gritti, Claudio Adragna . Analysis, design and performance evaluation of an LED driver with unity power factor and constant-current primary sensing regulation. AIMS Energy, 2019, 7(5): 579-599. doi: 10.3934/energy.2019.5.579
    [10] Vincent Katutsi, Milly Kaddu, Adella Grace Migisha, Muhumuza Ezra Rubanda, Muyiwa S Adaramola . Overview of hydropower resources and development in Uganda. AIMS Energy, 2021, 9(6): 1299-1320. doi: 10.3934/energy.2021060
  • This study evaluates the inconveniences raised by the installation of Shunt Capacitor Banks (SCB) along the North East Power System (NEPS) in Afghanistan. Besides the numerous advantages, a capacitor bank usually has some drawbacks in terms of transient currents which affect the quality of power supply and exceed the withstand capability of associated equipment. In this study, transient outrush current injects by installed SCB into the nearby faulted point at Pule Khumri and Chimtala substations is investigated. Outrush transient is produced by SCB when the breaker is operating to disconnect the faulted circuit. By applying different methods can mitigate outrush transient and protect the system which Current Limiting Inductance (CLI) is preferred in this study. Integrating CLI in series with SCB is the most relevant method which can limit the amplitude, frequency, and the rate of rise of the outrush transient. The use of inductance could otherwise create some excessive voltage which might exceeds the withstand capability of circuit breakers. Hence sensitivity analysis based on Transient Recovery Voltage (TRV) to confirm the robustness of the proposed approach is carried out. The evaluation is accomplished based on the result derived from the Electromagnetic Transients Program (EMTP), ATP package.


    Modern civilization severely depends on electrical energy for agricultural, commercial, domestic, industrial and social needs purposes. To avoid expanding the electrical systems, capacitor banks are widely installed across the existing networks. Using capacitor bank offers an economical method to provide voltage support, reactive power support, and to increase power transfer capability. They are also used to compensate the XI2 losses in transmission systems. Capacitor banks are comparatively cost-effective and can easily be installed anywhere on the electrical network. Generation capacity release; system capacity enhancement; power losses reduction; voltage regulation, and power quality improvement are the benefits that can be achieved by SCBs installation in electrical system [1].

    However, capacitor banks can create some inconveniences among which transient inrush/outrush current with a high amplitude and frequency is significant. Inrush current is produced due to load variation which results in several switching which are needed for connecting and disconnecting the capacitor bank in a typical day. Outrush current is produced when a breaker is operating to disconnect the nearby faulted circuit. The magnitude and frequency of discharged outrush current are dependent upon the total equivalent inductance between the capacitor bank and the faulted point. The inrush and outrush current conduct by a transient surge can affect the supply quality and exceed the withstand capability of the equipment [2,3,4,5].

    The propose of this study is, to analyse the inconveniences created by the installed SCBs along the NEPS in Afghanistan. Supply capacity in Afghanistan consists of import power and domestic hydro and thermal resources [6,7,8,9]. NEPS is the leading energy system, provides lower-cost power to cities and towns in the Northeast parts, including Kabul, the capital city. It encompasses import power from three neighbouring countries (Uzbekistan, Tajikistan, and Turkmenistan). NEPS, as the largest electrical system supplied 77% of all electricity demand in 2011. As the power system of exporter countries are not synchronised, it obliges the country to handle the NEPS in isolated regions which each unified with its nearby supplier. However, could all be interconnected if the supplier countries decided to operate either in synchronisation or agreed to interconnect through High Voltage Direct Current (HVDC) [10,11,12]. The existing and planned electricity grid in Afghanistan, is presented in Figure 1 [13].

    Figure 1.  Afghanistan existed and planned power system map [13].

    Due to unsynchronized operation of the system, a main part of the NEPS which is called NEPS-Uzbekistan is evaluated in this study. Depending on the grounding of the capacitor bank and types of the fault, the amplitude and frequency of the outrush transient can exceed the rating withstand limit of equipment and impose severe stress on the system. For further consideration two scenarios are evaluated to mitigate the outrush current generated by 25 Mvar and 120 Mvar capacitor banks at Pule Khumri and Chimtala substations respectively. To limit the amplitude and frequency, as well as the Rate of Rise of Outrush Current (RROC), CLI is integrated with each involved capacitor bank. As the use of CLI would otherwise create some excessive voltage, a sensitivity analysis based on Transient Recovery Voltage (TRV) is applied as well. The simulation for this study is performed by the Alternative Transients Program (ATP), which is a version of Electromagnetic Transient Program (EMTP).

    Capacitor banks are assembled by the series/parallel combination of capacitor units (Figure 2). Most of the capacitor banks at distribution and transmission level are Y connected and are either grounded or ungrounded, as shown in Figure 3. Capacitor banks are comparatively cost-effective and can easily be installed anywhere in electrical networks [14,15,16]. Besides their multiple benefits, capacitor banks can impose some inconveniences, which severely affect power quality on sensitive customer loads. It may also damage key equipment, potentially having a high impact on system reliability. To study dangers caused by transient inrush/outrush current, time-domain computer programs are developed [17,18].

    Figure 2.  Capacitor unit configuration [14].
    Figure 3.  Single and multiple Y connection of shunt capacitor units.

    Capacitor banks switching transients are becoming more critical especially with increasing the rate of its installations in power systems. This is because of frequent utility operations, occurring due to multiple switching per day and hundreds of time per year depending on the need for system voltage/var support from the capacitor banks. Switching a capacitor bank makes a change in circuit which a finite amount of time is required to approach a stable operating point. In capacitive discharge, there is a fixed energy amount depends on the stored capacity of involved capacitor banks just before switching and the amount store immediately after the event. Switching transient is produced due to voltage differences between the system and installed capacitor bank, characterized by high magnitude and frequency [19,20]. The maximum inrush current produce by SCB is derived from Eq (2.1). Transient inrush current has to be limited so as not to be harmful to the circuit breakers, capacitor bank, and the network. There are two possibilities to limit switching inrush current. The first one is to connect the capacitor at an exact time such that it can match the system voltage, and another way is to use a CLI in series with the capacitor bank [21,22].

    Imax=2×V×CBLS (2.1)

    where CB is the capacitance of the shunt capacitor bank, LS is system inductance, and V is a line to ground voltage.

    Transient outrush current with high amplitude and frequency is associated with a capacitor bank and the breaker when disconnecting a nearby faulted circuit. In capacitive discharge, there is a fixed amount of energy which depends on the energy stored in capacitance just before the event. In such a situation, depending upon the grounding of the capacitor bank and types of the fault, it can break the withstand capability limit of the circuit breaker, strike the capacitor bank and affect whole the system. The magnitude and frequency of outrush transient are dependent upon the total equivalent inductance between the capacitor bank and the fault, capacitor bank rating, and the point on the voltage waveform where the breaker disconnects the circuit [23,24,25]. For further evaluation, a typical system layout and an equivalent circuit are indicated in Figures 4 and 5, respectively. Use of CLI is an important discussion to mitigate the inrush/outrush current and protect the electrical systems. In Y connected systems, CLI can be used in different places between the switching device and the capacitor, between the bus and switching device, or between the end of each capacitor bnak and the neutral point. Technically it is also possible to distribute it throughout the capacitor bank (small inductors for each capacitor unit). Sizing the CLI should be done in such a way that the transient inrush/outrush currents through the switching device will not exceed its capability. The frequency and maximum capacity of outrush current are illustrated in Eqs (2.2) and (2.3) respectively [26,27,28].

    Figure 4.  System diagram.
    Figure 5.  Equivalent circuit for outrush current calculation.
    f=12ΠLeqC1 (2.2)
    ipk=V0×C1Leq (2.3)

    where; f is frequency of transient outrush current, C1 is the total capacitance of discharging capacitor bank, V0 is initial voltage of C1, L1 is self inductance of C1, L2 is inductance between capacitor and fault and Leq is equivalent inductance. For a three phase capacitor bank, a reasonable estimate of the peak outrush current is illustrated in Eq (2.4):

    ipk=10003πf×QckvarL (2.4)

    For 50 and 60 Hertz systems the equations are approximated as shown in the following equations:

    ipk=32QckvarL (2.5)
    ipk=43QckvarL (2.6)

    where; ipk is peak current [kA], f is power system frequency [Hz], Qc is capacitor bank rating [Kvar], and L is inductance per phase between capacitor bank and fault [μ H].

    Although hand calculations can make some estimations of capacitor outrush transients, an EMTP study is required to model the complex behaviours of the power system. Once the model is developed, many scenarios can be simulated and detailed statistical studies can be performed. In this study two scenarios are considered to investigate the challenges created by installed SCBs along NEPS. Through the first scenario, outrush current is evaluated during three phases to ground fault, nearby 25 Mvar capacitor bank in Pule Khumri substation (Figure 6). Based on simulation result, an outrush current is injected by the installed capacitor bank toward the faulted point when circuit breaker (S-PL-3) operates to disconnect the circuit. Outrush current produced with high amplitude (11.5 kA) and considerable rate of rising (2.61 kA/μs) as presented in Figure 7 can severely damage the circuit breakers and unstable whole the system. To properly visualize the negative impacts of installed SCB into a nearby fault, the same scenario is considered with ignoring capacitor bank, as result has shown in Figure 8.

    Figure 6.  Location of the fault and capacitor bank.
    Figure 7.  Outrush current injected by 25 Mvar SCB at Puli Khumri substation.
    Figure 8.  Fault current at Pul-e-Kumri substation when 25 Mvar SCB is disconnected.

    In the second scenario, the outrush current is evaluated by assuming three phases to ground fault at Chimtala substation, as presented in Figure 9. Based on calculation and simulation result, an outrush transient with a peak value of 6.5 kA and intensive rate of raising of 2.14 kA/μs is injected by the installed 120 Mvar SCB into the faulted point as shown in Figure 10.

    Figure 9.  Three phase to ground fault at Chimtala substation.
    Figure 10.  Peak and rate of rise of outrush current at Chimtala substation.

    To mitigate the injected outrush current as well as to protect the system, 3 mH and 2 mH inductors are applied in series with each considered capacitor banks in Pule Khumri and Chimtala substations respectively. The values of integrated CLIs are calculated based on trial and error experiments as well as a minimum/maximum allowable limit to fulfil the network's withstand capability. Diagram of the system and mitigated outrush current for each considered scenario is presented in Figures 1113, respectively.

    Figure 11.  Applied CLI capacity at Pule Kumri and Chimtala substations.
    Figure 12.  Limited outrush transient at Pole Khumri substation.
    Figure 13.  Limited outrush transient at Chimtala substation.

    CLIs application along NEPS provoke a possibility that if a fault occurs in such a way an excessive TRV can be imposed across the contacts of the circuit breaker when disconnecting the circuit. This is due to the high frequency of the inductor, which causes high-frequency oscillation on the load side of the circuit breaker when their is an attempt to interrupt the faulted circuit. TRV is a voltage, recovers or jumps back up to rated level across the contacts of a circuit breaker in electrical networks [29,30]. To confirm the robustness of the proposed approach, a sensitivity analysis based on TRV is applied in this study as well. For further evaluation, an EMTP calculation is performed to evaluate the TRV across the contacts of circuit breaker (S-PL-2) when a three-phase to ground fault considered in Pule Khumri substation. The result is shown in Figure 14 confirm that there is no excessive voltage produced by integrated CLIs on the NEPS.

    Figure 14.  TRV across terminals of circuit breaker (S-PL-2) in Pule Khumri substation.

    Fast transients due to inrush/outrush produce by capacitor banks causes a change in circuit configuration and create high di/dt in electrical networks. Transient currents and other power quality disturbances cause techno-economical losses due to damage of equipment and loss of electricity production. CLI can be used to reduce the di/dt and enhance, transient ground rise potentials. It often used in series with each capacitor bank to limit transient currents during switching (inrush current) or faults (outrush current). This study investigated the transient outrush current created by the installed SCBs along the NEPS in Afghanistan. For appropriate investigation, the calculations are performed by using EMTP, ATP package. Based on the simulation results, the energized SCBs are gating discharge with a high amplitude and frequency into the nearby fault when the associated circuit breaker is disconnecting the circuit. To mitigate the outrush transient and protect the system, a set of 3 mH and 2 mH CLI is integrated with both installed SCBs in Pule Khumri and Chimtala substations respectively [31].

    Sizing the fixed inductors has been done in such a way that outrush currents through the switching device would not exceed the device's capability. The values of CLIs are calculated based on trial and error experiments as well as a minimum/maximum allowable limit to fulfil the network's withstand capability. Limited outrush current for considered locations are indicated in Table 1. CLI integration otherwise may cause some unfortunate consequences by causing overvoltage that can fail circuit breakers. To limit the severity of the initial TRV across contacts of circuit breaker and confirm the robustness of the proposed approach, a sensitivity analysis based on TRV, is applied as well. Based on simulation result the peak and voltage acceleration associated with the initial TRV is less than that resulting from the ANSI-specified rate of rising of recovery voltage of 1.8 kV/μs [30].

    Table 1.  Outrush transient before and after CLI application.
    Capacitor locationImax [kA]RROC
    [kA/μ sec]
    Applied reactor
    [mH]
    Imax [kA]
    limited
    RROC
    [kA/μ sec]
    limited
    Puli Khumri11.52.6134.618.5
    Cimtala6.52.1424.315.3

     | Show Table
    DownLoad: CSV

    Though their are numerous advantage associated with the use of capacitor bank for voltage improvement in power system. However, it usually has some drawbacks in terms of transient currents which affect the quality of power supply and exceed the withstand capability of associated equipment. This paper investigated, inconveniences caused due to outrush current injected by capacitor banks into nearby faulted point along NEPS in Afghanistan. Enhancing the capability of associated equipment with higher dielectric tolerance to withstand outrush transient, require higher renovation cost, which is economically infeasible. The CLI integrated with each considered capacitor bank, successfully reduced the severity of outrush currents, enhanced the interrupting capability of circuit breakers and improved the quality of power supply. As the use of CLI would otherwise create some excessive TRV which could exceed the withstand capability of circuit breakers. Therefore, a sensitivity analysis based on TRV is applied to confirm the robustness of the proposed approach. This approach allowed the mitigation of outrush current problem without exceeding the TRV across contacts of circuit breakers. Overall the safety and reliability of the NEPS are enhanced by using the proposed configuration.

    For this paper, the authors acknowledge the support of the University of the Ryukyus through JICA (PEACE project).

    All authors declare no conflicts of interest in this paper.



    [1] Muromba N, Pudney D (2011) Shunt capacitor banks increase capacity of distribution networks. Energize 3: 30–33.
    [2] Iyambo PK, Tzoneva R (2007) Transient stability analysis of the IEEE 14-bus electric power system. AFRICON 2007 1–9.
    [3] Badrzadeh B (2013) Transient recovery voltages caused by capacitor switching in wind power plants. IEEE Trans Ind Appl 49: 2810–2819. doi: 10.1109/TIA.2013.2263491
    [4] Gopakumar G, Yan H, Mork BA, et al. (1999) Shunt capacitor bank switching transients: A tutorial and case study. Minnesota Power Systems Conference (No. 2–4).
    [5] Haginomori E (2003) Applied ATP-EMTP to highly-sophisticated electric power systems. Tokyou Institute of Technology and Kyushu Institute of Technology.
    [6] Jahangiri M, Haghani A, Mostafaeipour A, et al. (2019) Assessment of solar-wind power plants in Afghanistan: A review. Renewable Sustainable Energy Rev 99: 169–190. doi: 10.1016/j.rser.2018.10.003
    [7] Ibrahimi AM, Howlader HOR, Danish MSS, et al. (2019) Optimal Unit Commitment with Concentrated Solar Power and Thermal Energy Storage in Afghanistan Electrical System. Int J Emerging Electr Power Syst 20: 1–16.
    [8] Sediqi MM, Howlader HOR, Ibrahimi AM, et al. (2017) Development of renewable energy resources in Afghanistan for economically optimized cross-border electricity trading. AIMS Energy 85: 691–717.
    [9] Ibrahimi AM, Sediqi MM, Howlader HOR, et al. (2019) Generation expansion planning considering renewable energy integration and optimal unit commitment: A case study of Afghanistan. AIMS Energy 7: 441–464. doi: 10.3934/energy.2019.4.441
    [10] ICE Afghanistan 2019. Available from: https://sites.google.com/site/iceafghanistan/electricity-supply.
    [11] Irving J, Meier P (2012) Afghanistan resource corridor development: Power sector analysis. Australian AID.
    [12] April (2013) Power Sector Master Plan. Islamic Republic of Afghanistan, Ministry of Energy and Water.
    [13] Afghanistan Energy Information Center 2019. Available from: http://aeic.af/en/gismap/62.
    [14] Brunello G, Kasztenny B, Wester C (2003) Shunt capacitor bank fundamentals and protection. Conference for Protective Relay Engineers 1–17.
    [15] Issouribehere PE, Issouribehere F, Barbera GA, et al. (2007) Measurements and studies of harmonics and switching, transients in large HV shunt capacitor banks. Power Engineering Society General Meeting 1–8.
    [16] Hamouda A, Zehar K (2007) Improvement of the power transmission of distribution feeders by fixed capacitor banks. Acta Polytech Hung 4: 47–62.
    [17] Ali SA (2011) Capacitor banks switching transients in power systems. Energy Sci Technol 2: 62–73.
    [18] Samineni S, Labuschagne C, Pope J (2010) Principles of shunt capacitor bank application and protection. Protective Relay Engineers, 63rd Annual Conference 1–14.
    [19] Saied MM (2004) Capacitor switching transients: analysis and proposed technique for identifying capacitor size and location. IEEE Trans Power Delivery 19: 759–765. doi: 10.1109/TPWRD.2003.822953
    [20] Grebe TE (1996) Application of distribution system capacitor banks and their impact on power quality. IEEE Trans Ind Appl 32: 714–719. doi: 10.1109/28.502186
    [21] Blooming TM, Carnovale DJ (2007) Capacitor application issues. Conference Record of 2007 Annual Pulp and Paper Industry Technical Conference 178–190.
    [22] NEPSI 2019. Available from: https://www.scribd.com/document/347247617/Peak-Capacito-Bank-Out-Rush-Current-Calculation-xlsx.
    [23] Paul W, Chen M, Lakner M, et al. (2001) Fault current limiter based on high temperature superconductors different concepts, test results, simulations, applications. Phys C: Supercond 354: 27–33. doi: 10.1016/S0921-4534(01)00018-1
    [24] De Metz-Noblat B, Dumas F, Poulain C (2005) Cahier Technique no. 158: Calculation of Short-Circuit Currents. Schneider Electric, updated.
    [25] Boutsika TN, Papathanassiou SA (2008) Short-circuit calculations in networks with distributed generation. Electr Power Syst Res 78: 1181–1191. doi: 10.1016/j.epsr.2007.10.003
    [26] Akinrinde AO, Swanson A, Tiako R (2016) Transient analysis and mitigation of capacitor bank switching on a standalone wind farm. World Acad Sci, Eng Technol, Int J Electr, Comput, Energ, Electron Commun Eng 10: 535–544.
    [27] Stankovic AM, Aydin T (2000) Analysis of asymmetrical faults in power systems using dynamic phasors. IEEE Trans Power Syst 15: 1062–1068. doi: 10.1109/59.871734
    [28] Meyer C, Schroder S, De Doncker RW (2004) Solid-state circuit breakers and current limiters for medium-voltage systems having distributed power systems. IEEE Trans Power Electron 19: 1333–1340. doi: 10.1109/TPEL.2004.833454
    [29] Liu H, Wang Z, Yang J, et al. (2018) Circuit breaker Rate-of-Rise recovery voltage in Ultra-High voltage lines with hybrid reactive power compensation. Energies 11: 100. doi: 10.3390/en11010100
    [30] Bellei TA, Camm EH, Ransom G (2001) Current-limiting inductors used in capacitor bank applications and their impact on fault current interruption. 2001 IEEE/PES Transmission and Distribution Conference and Exposition 1: 603–607. doi: 10.1109/TDC.2001.971302
    [31] Harlow JH (2007) Electric Power Transformer Engineering.
  • Reader Comments
  • © 2019 the Author(s), licensee AIMS Press. This is an open access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0)
通讯作者: 陈斌, bchen63@163.com
  • 1. 

    沈阳化工大学材料科学与工程学院 沈阳 110142

  1. 本站搜索
  2. 百度学术搜索
  3. 万方数据库搜索
  4. CNKI搜索

Metrics

Article views(5509) PDF downloads(944) Cited by(0)

Figures and Tables

Figures(14)  /  Tables(1)

/

DownLoad:  Full-Size Img  PowerPoint
Return
Return

Catalog