Research article Topical Sections

Energy efficient measure to upgrade a multistory residential in a nZEB

  • Developing nearly Zero Energy Buildings (nZEB) represents a path toward sustainable communities as required by the Energy Performance of Building Directive (EPBD). As consequence, nZEB target for new or existing buildings has become a mandatory priority for the multidisciplinary researchers involved in architectural engineering and building physics. Therefore, it is grown the interest in design energy efficient measures for reaching the nZEB status of both new and existing buildings. In this paper, the energy efficient measures adopted for reaching the nearly Zero Energy Building standards, for a multi-floor residential building located in the Mediterranean area, are presented. The extra cost necessary to reach the nZEB target have been calculated in the case of the energy retrofit of an existing building (scenario 1) and in the case to directly realize a building with achieve the nZEB status (scenario 2). Further, the two scenarios have been compared under financial point of view. The results of this paper provide to builders and stakeholder useful information for quantify the convenience to build a nZEB building in advance in order to prevent the additional expenses necessary by future energy retrofit programs.

    Citation: Antonio Gagliano, Salvatore Giuffrida, Francesco Nocera, Maurizio Detommaso. Energy efficient measure to upgrade a multistory residential in a nZEB[J]. AIMS Energy, 2017, 5(4): 601-624. doi: 10.3934/energy.2017.4.601

    Related Papers:

    [1] Badr Ouhammou, Fatima Zohra Gargab, Samir El idrissi kaitouni, Slimane Smouh, Rachid El mrabet, Mohammed Aggour, Abdelmajid Jamil, Tarik Kousksou . Energy saving potential diagnosis for Moroccan university campuses. AIMS Energy, 2023, 11(3): 576-611. doi: 10.3934/energy.2023030
    [2] Nadejda Komendantova, Markus Manuel Schwarz, Wolfgang Amann . Economic and regulatory feasibility of solar PV in the Austrian multi-apartment housing sector. AIMS Energy, 2018, 6(5): 810-831. doi: 10.3934/energy.2018.5.810
    [3] Alemayehu T. Eneyaw, Demiss A. Amibe . Annual performance of photovoltaic-thermal system under actual operating condition of Dire Dawa in Ethiopia. AIMS Energy, 2019, 7(5): 539-556. doi: 10.3934/energy.2019.5.539
    [4] Kaovinath Appalasamy, R Mamat, Sudhakar Kumarasamy . Smart thermal management of photovoltaic systems: Innovative strategies. AIMS Energy, 2025, 13(2): 309-353. doi: 10.3934/energy.2025013
    [5] Angelo Minotti . Hybrid energy converter based on swirling combustion chambers: the hydrocarbon feeding analysis. AIMS Energy, 2017, 5(3): 506-516. doi: 10.3934/energy.2017.3.506
    [6] Daniel Chuquin-Vasco, Cristina Calderón-Tapia, Nelson Chuquin-Vasco, María Núñez-Moreno, Diana Aguirre-Ruiz, Vanesa G. Lo-Iacono-Ferreira . Mathematical modeling of a binary ORC operated with solar collectors. Case study—Ecuador. AIMS Energy, 2023, 11(6): 1153-1178. doi: 10.3934/energy.2023053
    [7] Jin H. Jo, Jamie Cross, Zachary Rose, Evan Daebel, Andrew Verderber, David G. Loomis . Financing options and economic impact: distributed generation using solar photovoltaic systems in Normal, Illinois. AIMS Energy, 2016, 4(3): 504-516. doi: 10.3934/energy.2016.3.504
    [8] Sergio Copiello . Economic viability of building energy efficiency measures: a review on the discount rate. AIMS Energy, 2021, 9(2): 257-285. doi: 10.3934/energy.2021014
    [9] Jin H. Jo, Zachary Rose, Jamie Cross, Evan Daebel, Andrew Verderber, John C. Kostelnick . Application of Airborne LiDAR Data and Geographic Information Systems (GIS) to Develop a Distributed Generation System for the Town of Normal, IL. AIMS Energy, 2015, 3(2): 173-183. doi: 10.3934/energy.2015.2.173
    [10] Muti Ur Rehman Tahir, Adil Amin, Ateeq Ahmed Baig, Sajjad Manzoor, Anwar ul Haq, Muhammad Awais Asgha, Wahab Ali Gulzar Khawaja . Design and optimization of grid Integrated hybrid on-site energy generation system for rural area in AJK-Pakistan using HOMER software. AIMS Energy, 2021, 9(6): 1113-1135. doi: 10.3934/energy.2021051
  • Developing nearly Zero Energy Buildings (nZEB) represents a path toward sustainable communities as required by the Energy Performance of Building Directive (EPBD). As consequence, nZEB target for new or existing buildings has become a mandatory priority for the multidisciplinary researchers involved in architectural engineering and building physics. Therefore, it is grown the interest in design energy efficient measures for reaching the nZEB status of both new and existing buildings. In this paper, the energy efficient measures adopted for reaching the nearly Zero Energy Building standards, for a multi-floor residential building located in the Mediterranean area, are presented. The extra cost necessary to reach the nZEB target have been calculated in the case of the energy retrofit of an existing building (scenario 1) and in the case to directly realize a building with achieve the nZEB status (scenario 2). Further, the two scenarios have been compared under financial point of view. The results of this paper provide to builders and stakeholder useful information for quantify the convenience to build a nZEB building in advance in order to prevent the additional expenses necessary by future energy retrofit programs.


    Nomenclature
    c specific heat and thermal capacity (kJ/kg·K)
    C cost (€)
    D Debt (€)
    DPP Discount Pay Back (year)
    E Equity (€)
    ERR External Rate of Return (€)
    ES Energy saving (kWh)
    ERES annual renewable energy (kWh)
    g Solar factor (-)
    h Height (m)
    h0 Coefficient of adduction (W/m2·K)
    id Opportunity cost of Equity (-)
    ie Interest rate for Debt (-)
    IRR Internal Rate of Return (€)
    MS Superficial Mass (kg/m2)
    NPV Net Present Value (€)
    PE Primary energy (kWh/m2·y)
    PI Cost of the investment (€)
    PIT Point input (€)
    PP Payback period (year)
    Q Energy needs (kWh)
    Qusable Total usable heat delivered by HPs (kWh)
    r Discounted rate (-)
    rf Reflectance of vegetation layer (-)
    rs Minimum stomatal resistance (s/m)
    R Revenues (ε)
    Ri Thermal resistance of a masonry (m2·K/W)
    s Thickness (m)
    S Surface (m2)
    SPF Seasonal Performance factor (-)
    t Time (year)
    tf Transmissivity of vegetation layer (-)
    T Life Cycle (year)
    To Outdoor air temperature (℃)
    Tsi Indoor surface temperature (℃)
    Tso Outdoor surface temperature (℃)
    U Thermal transmittance (W/m2·K)
    V Heated gross volume (m3)
    Y Periodical thermal transmittance (W/m2·K)
    w Cost of Capital (€)
    W Weighted Average Cost of Capital (€)
    Greek letters
    α Absorbance (-)
    β Tilt (°)
    η Efficiency (-)
    λ Thermal conductivity (W/m·K)
    ε Emissivity (-)
    ρ density (kg/m3)
    θ Moisture content (m3/m3)
    Ψ Linear thermal transmittance (W/m·K)
    Subscripts
    C Cooling
    e External
    f Foliage
    g Ground
    g, H Globally for heating
    gl Heating + Production of hot water
    H Heating
    i Internal
    ie Internal-external
    ij Intervention "j" at the "i" month
    p Constant pressure
    RE Renewable Energy
    Sat Saturation
    u Net floor area
    V Ventilation
    w Window
    W Production of hot water
    Acronyms and Abbreviations
    ACs Air Conditioning system
    BIPV Building Integrated Photovoltaic
    CB Condensing Boiler
    DCF Discounted Cash Flow
    DHW Domestic Hot Water
    EPBD Energy Performance of Building Directive
    ETICS External Thermal Insulation Composite Systems
    EU European Union
    GR Green roof
    HP Heat Pump
    HPs Heat Pump system
    mESE Multiplicative Energy Saving Effects
    nZEB Nearly Zero Energy Building
    PV Photovoltaic
    RES Renewable Energy Sources
    S1HS1 New building with Condensing Boiler
    S1HS2 New building with Heat Pump
    S2HS1 Retrofit with Condensing Boiler
    S2HS2 Retrofit with Heat Pump
    ST Solar Thermal
    TB Thermal Bridge
    TI Thermal Insulation
    TR Traditional roof
    VF Ventilated Facades
    WI Low-E Reflective windows

    1. Introduction

    The Energy Performance of Buildings Directive (EPBD) requires all new buildings to be nearly zero-energy by the end of 2020, while new public buildings must be nearly zero-energy by 2018 [1].

    Further, policies and measures to stimulate the refurbishment of the existing building stock into nZEB are also required.

    The energy performance of existing buildings is expressed in terms of their annual specific primary energy consumed, which falls in the range of 150–400 kWh/m2 per year for residential buildings and 250–550 kWh/m2 per year for office buildings [2]. Such energy needs are enormous compared with the standards of 40–60 kWh/m2 per year set for low energy buildings.

    As result, plenty of papers were devoted for identifying cost-effective energy efficient measure promoting low energy consumption. Hamdy [3] applied a method to find the cost-optimal and nZEB energy performance levels for a study case of a single-family house in Finland. He considered different options of building-envelope parameters, heat-recovery units, and heating/cooling systems as well as various sizes of thermal and photovoltaic solar systems as design options. The economic and environmental trade-offs show that primary energy consumption ≥ 93 and ≤ 103 kWh/m2 is a cost-optimal energy performance level in Finland. Georges et al. [4] investigated a single-family dwelling in Belgium, addressing combinations of sixteen heating systems and five building designs. Marszal and Heiselberg [5] found the minimum life-cycle cost for a multi-storey residential net-zero-energy building in Denmark, addressing three levels of energy demand and three alternatives of energy supply systems.

    The concept of nZEB refers to a building with a net energy consumption of nearly zero over a typical year. The target of a nZEB is not limited to minimize the energy consumption with energy efficient envelope and the rational use of energy (RUE), but requires balancing their energy requirements exploiting of on-site renewable sources, locally available, non-polluting, low-cost [6,7,8].

    Therefore, nZEB are buildings connected to any energy infrastructure with which they realize a bilateral energy flux. The connection to an energy infrastructure introduces the issues of the building/grid interaction [9], as well as the balance between delivered and exported energy. Figure 1 depicts the connections between building and energy grids [10].

    Figure 1. Connection between building and energy grid rearranged by [11].

    The Primary Energy (PE) is the metric adopted for making the balance between energy needs and renewable energy production (PERE). The energy needs are those related to space heating (PEH) and cooling (PEC), production of hot water (PEW), ventilation (PEV) and lighting (PEL). Consequently, the following expression holds:

    PE=year(PEH+PEW+PEC+PEV+PELPERE) (1)

    The result of equation (1) shall be almost zero in order to center the target of nZEB buildings. In literature, energy calculation methodologies [12,13], system design [14,15] integration with renewable energies [16], as well as system control/management optimization for reach the nZEB target are presented [17,18,19]. Moreover, an important issue is the economic feasibility of the energy efficiency measure to reach the nearly zero energy buildings status.

    The economic features of sustainability in architecture involve practical and symbolic values that monetary valuation captures only partially and multidimensional analyses are welcome [20]. Nonetheless, many applications in the ground of architectural design and urban planning confirm that economic and financial indices play a significant role of morphogenetic variables [21], whereas at the basic level, the monetary quantitative approach aims at minimizing the investment cost given the energy saving goal.

    As the energy retrofit programs are typically characterized by large starting expenses, the correct and systematic economic assessment of these investments is an important basis for choosing the energy efficient measures most suitable to the needs and financial possibilities of homeowners who—not being professional investors—needs of clear guidance about the environmental and economic balance.

    In the outlined perspective, the economic issue works as a sort of double interface: downward, with the natural and technological sphere; upward, with the political sphere. In fact: on the one hand, natural environment provides some boundaries and constraints to the human behavior that economy transforms in rational commitments; on the other hand, economics provides useful tools to the policy, making possible what is convenient just for some, thus balancing individual rationality and collective intelligence.

    Furthermore, in geographical areas with different climate according to the costs of the technological equipment, gas and electricity market price, the decrease of the energy needs in heating and cooling are differently welcomed, so that some technologies and processing times are preferred, some others excluded, despite the general environmental effectiveness that makes them highly recommended by the EU regulations.

    This paper analyses a set of energy efficient measures broadly adopted nowadays, which allow reaching the nZEB target for a residential multistore building.

    Two different scenarios have been analyzed that are the energy retrofit of an existing building (scenario 1) and to build in advance a new one (scenario 2), considering in both cases, the extra cost necessary to reach the nZEB target. Further, the two scenarios have been compared under financial point of view. The novelty of this paper is to provide to builders and stakeholder useful information for quantify the convenience to build a nZEB building in advance in order to prevent the additional expenses necessary by future energy retrofit programs.


    2. Materials and Method

    As well known, the achievement of the energy and environmental target established for nZEB can be reached through possible combinations of energy efficient measure.

    In this paper, a set of widespread and suitable solutions have been selected for the refurbishment of multi-story residential building located in mild climate area. Thus, in the following paragraph, the authors describe:

    (1) the systems and technologies proposed to reduce the energy needs of buildings;

    (2) the software used for calculating the energy performance to achievement the target of nZEB;

    (3) the economic analysis for evaluating of the financial feasibility and economic convenience of the investments.


    2.1. Systems and technologies

    The external wall insulation systems (ETICS), "Low-E and reflective" windows, load bearing thermal insulation element, ventilated façades and green roofs are widespread constructive techniques frequently implemented for realizing the building envelope of an nZEB, as well condensing boilers (CB) and a Heat Pumps (HP) are the energy generation system used for space heating and domestic hot water.

    As regard the renewable energy plant photovoltaic and a solar thermal plants are two technologies often implemented.


    2.2. Simulation software

    The energy needs (Q) and Primary energy (PE) for Heating, Cooling and DHW have been calculated through MasterClima Software [22], which operates in accordance with EN 15316, UNITS 11300 parts 1–4. DesignBuilder Software was used for simulating the performance of green roofs [23].


    2.3. Economic analysis

    The economic analysis aims at optimizing the bundle of technical solutions to hit the target of nZEB standard considering the set of constraints externalities (costs, taxes etc.) and opportunities (energy market prices, incentives etc.).

    According to the two main issues of the economic-financial approach—financial feasibility and economic convenience—a two-stages methodology has been developed. The first stage (A) take into account of cost and revenues; the second stage (B) concerns the economic and financial analysis of the different technologies implemented.


    2.3.1. Cost of the nZEB program (first stage)

    The costs of the nZEB program is constituted by manpower, materials, equipment, design and work supervisor, while the revenues come from government incentives and the energy savings. The costs of manpower, materials, and equipment have been obtained from price list or market surveys.

    The budgets for the refurbishment have to include the needs for temporary structures, such as scaffoldings, and the costs for removing the existing equipment (i.e. external plasters, window frames, HVAC plant and so on).

    The maintenance costs are: Thermal Insulation (TI) 1.00%; Windows (WI) 0.50%; Ventilated Facades (VF) 0.00%; Green Roof (GR) 1.00%; Condensing Boiler (CB) 2.00%; Heat Pump (HP) 1.00%; Thermal Solar plant (ST) 1.00%; Photovoltaic (PV) 0.01%; Thermal Bridge (TB) 1.00%.

    Design and work supervisor accounts for a percentage of about 10% of the total costs of the interventions.

    The revenues come from energy savings, have been accounted at the current prices of gas (0.80 €/Nm3) and electricity (0.17 €/kWh).

    The refurbishment scenario can count on the government incentive, which accounts by 65% of the cost of the energy efficient measure (including design and supervisor costs). This incentive is fragmented in ten annual quotas starting from the first year.


    2.3.2. Discounted cash flow analysis (second stage)

    A discounted cash flow analysis [24,25] allows measuring and comparing the financial attractiveness of the two proposed scenarios. In particular, the following financial indices have been evaluated.

    (1) Net Present Value (NPV), it is the sum of the discounted values of incoming and outgoing cash flows, that are revenues (R) and costs (C), discounted by the rate (r) during the time period (T):

    NPV=Tt=0RtCt(1+r)t (2)

    In order to compare different options with almost equal (NPV), (r) has to be assumed equal to the cost of capital, which can be calculated according to the Weighted Average Cost of Capital (WACC):

    rwWACC=idD+ieED+E (3)

    Where: (w) is the cost of the invested capital, (id) is the interest rate for Debt (D) and (ie) is the opportunity cost of Equity (E).

    The interest rate for Debt and the opportunity cost of Equity are referred respectively to the active and passive interest rates charged to households and consumers, according to the statistics of Bank Italia (2015), set at 4.66% (over 5 years loan life) and 0.12%; assuming a leverage ratio of 50%. Consequently, the value of WACC is 2.39%.

    (2) The External Rate of Return (ERR), is the discount rate by which the future value of the point input (PIT) at the end of the life cycle (T) is equal to the future value of the positive cash flows invested at the Minimum Attractive Rate of Return (MARR) [25] that in this case is assumed equal to (w):

    ERR=t1PI(1+w)tTt=0(RtCt)(1+w)t1 (4)

    ERR has to be greater than (w) so that, assuming as relevant this criterion, the decrease of the Debt interest rate could help the financial feasibility of the nZEB program.

    (3) The Internal Rate of Return (IRR) is the discount rate that makes (NPV) of all cash flows from the investment equal to zero:

    Tt=0(RC)t(1+IRR)t=0 (5)

    It corresponds to the maximum rate of return of an investment assuming the discount rate equal to zero. The IRR depends on the distribution of the costs and revenues along the lifecycle of the investment; (IRR) needs to be greater than discount rate, given that the discount rate is assumed as the global cost (interest rate and opportunity cost) of the invested capital (w).

    (4) The Discounted Payback Period (DPP) or simply Payback Period (PP) is the length of time (T*) required to recover the cost of the investment (PI), calculated with (r > 0) [26] or without (r = 0) [27]; the higher the discount rate, the longer the (DPP).

    DPP can be calculated as the ratio between the discounted outgoing cash flow and the annual average incoming:

    DPP=Tt=0Ct(1+w)tTt=0RtwqT(1+w)tqt1 (6)

    In equation (6) the denominator is the average annual income, calculated by transforming the discounted variable revenue stream in a constant rate, and q = 1 + w.

    The above mentioned indices have been calculated both for each component of the nZEB program and for the program as a whole, in order to allow procurers to make informed decisions about the best allocation of the available budget.


    3. Test Case

    The case study used as reference is a multi-storey residential building with 39 apartments located in Sicily (Acireale; latitude 15°9', longitude 37°36'). The building consists of three floors above ground and it is subdivided in five blocks. The blocks 1, 3 e 4 have three apartments for each floor, (total 27 units), instead the blocks 2 and 5 have two apartments for floor (total 12 units).

    Figure 2 and Table 1 show the existing building and its main geometric data.

    Figure 2. a) East façade; b) South-East prospective; c) South façade.
    Table 1. Geometric data and characteristic parameters.
    Heated gross-volume V 12580, 88 m3
    Surface/volume coefficient S/V 0,417 l/m
    Net floor area Su 3189 m2
    Ventilation rate - 0.30 vol/h
     | Show Table
    DownLoad: CSV

    As regard, the ventilation the air change rate of 0.30 vol/h has been adopted, since it is typical of a building under natural ventilation condition. The current rules on building energy efficiency impose specific thresholds of thermal insulation of the building envelope components as well as limits to the primary energy needs, and do not impose the achievement of the target of NZEB. Thereby, the U-values (thermal transmittance) and Ψ-values (thermal transmittance per unit length) of the components of a standard building envelope must satisfy the threshold reported in Table 2 (Italian climatic zone C).

    Table 2. Geometric data and features.
    External wall Roof slab Ground floor Glazing surfaces
    Uvalue (W·m–2·K–1) 0.43 0.41 0.43 3.16
    Thermal bridge
    Ψ (W·m–1·K–1) 0.80
     | Show Table
    DownLoad: CSV

    3.1. Energy needs of the test case building

    The energy needs of the test building has been calculated through the software Masterclima, which allow to calculate the terms PEH, PEW and PECin equation (1).

    The energy needs are calculated assuming an internal design temperature of 20 ℃ during the heating period (15st November–31th March) and 26 ℃ during the cooling period (1st April–15th November). The daily hot water needs have been evaluated in 150.00 l/day per apartments.

    The thermal energy for heating space and DHW (Domestic Hot Water) production are both provided through combined centralized gas-fired system with a seasonal average yield, called global efficiency (ηg, H) of 77.80%. The standard building configuration has the following energy needs: QH = 155.55 MWh; QW = 55.19 MWh; QC = 89.86 MWh.

    The primary energy for heating, QP, H = 199.832 MWh, and DH, QP, W is 70.873 MWh, area obtained introducing the global efficiency of the heating system. Thus, the primary specific energy for space heating (PEH) and DHW production (PEW) are:

    PEH=QHηg,HSu=62.66kWh/m2y (7)
    PEW=QWηg,HSu=22.22kWh/m2y (8)

    PEcis a specific useful energy for cooling space of building and it is given by:

    PEC=QCSu=28.17kWh/m2y (9)

    Where (Su) is net floor area of whole building equal to 3,189 m2.Therefore, global primary specific energy needs (PEgl) is calculated as follows:

    PEgl=PEH+PEW=84.882kWh/m2y (10)

    Thus, if the buyer would like upgrade this test building in an nZEB configuration the adoption of energy efficient measures is necessary. Now, two possible alternative emerge, the first one is the refurbishment of this standard configuration (scenario 1) and the second is the implementation of the energy efficient measure directly in advance when the building is build (scenario 2).


    4. Performance of the Upgraded Building


    4.1. Building envelope

    The energy performance of the test building has been improved applying the constructive technologies previously mentioned.

    New windows are realized in aluminum with thermal break and double glazing composed by two panes of 6 mm and 16 mm of air gap between panes. The U-value of the windows is calculated in according to UNI EN ISO norms [28,29].

    As regard the ETICS a thickness of 3 cm of thermal insulations has been added, and consequently an additional thermal resistance of 0.70 W/m2·Kis achieved.

    Table 3. Main features of Low-E and reflective windows.
    Double glass (s = 28 mm) two 6 mm glass and 16 mm airspace
    Glazing Ug (W/m2·K) Frame Uf (W/m2·K) Window Uw (W/m2·K) Solar factor g (%) Emissivity of glass ε (-) Reflectance r (-)
    1.30 2.89 2.00 42 0.1 0.9
     | Show Table
    DownLoad: CSV

    A ventilated façade is constituted by an air gap, with thickness of 10 cm, and Poroton blocks where is fixed the bearing structure of panels. Substantially, the ventilated facades act reducing the energy needs for cooling through the combined action of shading of the external walls, from the incident solar radiation, and the ventilation of the air channel due to the air buoyancy. The U-value was calculated by means UNI EN ISO 6946 [30] as reported in the following equation:

    U=11hoe+ni=1siλi+1hoi (11)

    For the ventilated facades, the U-valueis obtained neglecting the thermal resistance of the air gap and all layers that separate it from outdoor air. Consequently, the thermal resistance of the internal layer (∑sii) and the two superficial thermal resistance, hoe and hoi, are included. Therefore the U-value of the ventilated facade results by 0.30 W/m2·K. Moreover, the thermal mass (MS = 262 kg/m2), Thermal Capacitance (Ci = 38.83 kJ/kg·K) and Periodic Thermal Transmittance (Yie = 0.07 W/m2·K) have been calculated.

    The layers reported in Table 4 constitute the implemented extensive green roof, where mosses, an essence that guarantee a good coverage as well as roof membrane protection, constitute the vegetation layer [30].

    Table 4. Main features of the green roof.
    Layer a b c d e f g h
    Vegetation layer Growing Medium (15 cm) Filter layer (0.1 cm) Drainage (10 cm) Water proofing membrane Thermal insulation (6 cm) Moisture barrier (0.5 cm) Roof deck (10 cm)
     | Show Table
    DownLoad: CSV

    The thermo-physical features of the vegetation layer and substrate are reported in Table 5.

    Table 5. Thermo-physical properties of vegetation and substrate layer.
    Vegetation layer
    Height of the plants (hf) (m) Leaf are index (LAI) (m2/m2) Albedo (rf) Absorbance (αf) Transmissivity (tf) Emissivity (εf) Minimum Stomatal Resistance (rs) (s/m)
    0.10 2.0 0.22 0.60 0.18 0.95 180
    Substrate
    Thermal conductivity (λg) (W/m2·K) Density (ρg) (kg/m3) Specific heat (cp) (J/kg·K) Absorbance (αg) Emissivity (εg) Moisture Content (θ) (m3/m3) Saturation Moisture (θsat) (m3/m3)
    0.98 0.98 880 0.70 0.90 0.40 0.60
     | Show Table
    DownLoad: CSV

    The U-value of the green roof is 0.20 W/m2·K. Moreover, the thermal mass (MS = 602 kg/m2), thermal capacitance (Ci = 70.20 kJ/kg·K) and periodic thermal transmittance (Yie = 0.12 W/m2·K) have been calculated in accordance to UNI EN ISO 13786:2008 [31].

    Table 6 summarize the U-value of the components of the envelope of the upgraded building for the two scenarios.

    Table 6. Opaque envelope and glazing thermal features.
    Type U (W/m2·K) Ψ (W/mK)
    Ventilated Facades 0.30 -
    Green Roof 0.20 -
    External Wall Insulation Systems 0.33 -
    Low-E and Reflective Windows 2.00 -
    Thermal bridge - 0.15
     | Show Table
    DownLoad: CSV

    Figure 3 shows the monthly energy saving (ESJ)I associated with each investigated energy efficient measure.

    Figure 3. Energy saving attained by each building components.

    It can be noted that the ETICS provides the highest energy savings during the heating period; otherwise, it implies the growth of the energy needs during the months of April, May, September and October. This happens because of the indoor set point temperature, used in calculation, is fixed at 26 ℃ (according UNI TS 11300), that could be higher than the outdoor temperatures. Accordingly, the thermal flux goes from the indoor to outdoor environment and the increase of the thermal resistance impedes the cooling of the internal environment, especially during the night time. Otherwise, in July and August the outdoor air temperatures are highest than the indoor temperatures, therefore the increase of thermal insulation reduce the thermal flux form the outdoor to the indoor environment.

    The low-e and reflective windows allow getting excellent performances during the cooling period contributing by 50% of the reduction of the cooling needs, thanks mainly to the reduction of solar gains.

    The ventilated façades give a support to the energy saving all year around, and are most efficient during the summer months (June, July, August and September), contributing by 24% of the reduction of the cooling needs. Table 7 shows the reduction of the energy needs and specific primary energy associated with each energy efficient measure as well as the whole package.

    Table 7. Reduction of the energy needs and specific primary energy.
    Intervention ΔQH(MWh) ΔQC(MWh) ΔPEH(kWh/m2y) ΔPEC (kWh/m2y)
    ETICS 80.97 +34.12 32.63 +10.70
    Windows 4.27 28.35 1.72 8.89
    Ventilated Facade 4.22 10.10 1.70 3.17
    Green roof 2.75 4.25 1.11 1.33
    Whole package of EEM 107.87 30.88 43.48 9.68
     | Show Table
    DownLoad: CSV

    Globally, the proposed package of energy efficient measure reduces by 69% the energy needs for space heating, (107.87 MWh), and by 34% (30.88 MWh) for space cooling. This result is higher than the summation of the energy saving deriving from each energy efficient measure thanks to a "multiplicative Energy Saving Effects" (mESE).

    Globally, the energy needs of the building envelope, which include the above described energy efficient measure are QH = 47.31 MWh; QC = 58.79 MWh. As regard the energy needs for DHW production there are not variation, QW = 55.19 MWh.

    Thereby, the equation (1) for the upgraded building gives the following indexes of energy performance, which are PEgl = 41.28 kWh/m2y; PEC = 18.43 kWh/m2y. To further reduce the energy needs it is necessary improve the efficiency of the energy production system and foresee the exploitation of RES.


    4.2. Energy production systems

    The energy performance of building can be further increased through the introduction of generation systems with efficient higher than the traditional generation system that are a condensing boiler and one Heat Pumps.

    Therefore, the energy needs of the upgraded building have been calculated installing an air source vapor compressed HP with a seasonal performance factor (SPF) of 3.45, or a condensing boiler (CB) with an efficiency of 99.0% are implemented as heating generation systems.

    The specific primary energy PEH becomes 11.52 kWh/m2yand 14.03 kWh/m2y in the case of a (HP) or a (CB) respectively.

    The EU directive [32] recognizes Heat Pumps (HPs) as a technology that exploit RES from air, water and ground, when the efficiency of HP, calculated with reference to the primary energy, is higher than 115%. This means that the SPF must satisfy the follows condition:

    SPF>1.15η (12)

    Where η is the efficiency of electricity production in the EU, here assumed equal to 0.4.

    The annual renewable energy (ERES) delivered by the HP, calculated by equation 14, is of 33.62 MWh, which is about the 71% of the thermal energy request for space heating.

    ERES=Qusable(11SPF) (13)

    Where (Qusable) is total usable heat delivered by HPs for space heating and Domestic Hot Water (DHW).

    However, the implementation of a heat pumps resets the fuel needs but involves a demand of electric energy that will be satisfied by the optimal management of various RES.


    5. Renewable Energy


    5.1. Solar thermal plant

    The energy needs for DHW represents a significant percentage of the total energy demand of the building. Indeed, the primary energy for domestic hot water PEW amounted to 22.22 kWh/m2y that is about 50% of the global primary energy PEgl in the case of the upgraded building envelope.

    Thus, the installation of 39 thermal solar plants, with a gross area of 3.00 m2, has been accounted for reducing the DHW energy requirement. The solar collectors are south oriented with a tilt angle of 35°, the collector's optical efficiency (τα) is of 86%, and the coefficient of thermal losses is 3.50 (W/m2·K). Moreover, each solar plants equipped with a stratified storage tank with a capacity of 250.00l.

    The monthly average daily values of solar radiation incident on the solar plants was evaluated by the National Institute for Alternative Energy (ENEA) software [33].

    Starting by the previous mentioned data, the calculation developed by the "f chart" method [34] have shown that the surface of 3.00 m2is sufficient to satisfy by 80% of the DHW energy demand of each apartments. Figure 4 reports energy provided and the fraction of energy needs satisfied by each solar thermal plant.

    Figure 4. Solar fraction and energy produced for DHW by the solar thermal plant.

    In this way, the request of energy for DHW is 4.44 kWh/m2yand, consequently the global specific primary energy PEgl is drastically reduced to 17.70 kWh/m2ywhen the heating system is a HP and 23.50 kWh/m2y when the heating system is a CB. The effectiveness of these interventions on systems is an important issue for buildings that are located in temperate climates, for which the interventions on the building envelope are costly and not decisive in terms of energy savings.


    5.2. Nearly zero energy building

    The target of a nZEB is not only to minimize all the energy consumption, including energy requirements for lighting and other use such as the plug loads, but also balances its energy requirements with the local production of energy through RES.

    The total demand of electrical energy is about 117,000 kWh, which was calculated assuming an electricity energy consumption of about 3.000 kWh/y per apartment [35].

    For this purpose, the implementation of a BIPV (Building integrated photovoltaic) plant has been evaluated. The PV panels are posed on the facades and on the parapets of the balconies (β = 90°) of each apartment, as well as on the roofs of the staircases (β = 15°). The PV technology used is the crystalline silicon and its characteristics and geometric data are reported in Table 8.

    Table 8. Characteristics and geometric data of PV panels.
    Efficiency PV (ηPV) Dimension (m × m) Surface (m2) Peak power* (W) Panel surface for kWp installed power (m2) Number of panels for kWp
    14% 1.65 × 1.00 1.65 250 6.53 4
    *The peak power is referred to a standard condition: temperature of 25 ℃ and solar radiation of 1000 W/m2.
     | Show Table
    DownLoad: CSV

    Figure 5 and 6 show the positioning of the PV panels in a representative block of the multistore building and a view of the building façade in which the BIPV plants are implemented.

    Figure 5. Building after renovation: a) West façade; b) 3D view and South façade; c) South facade.
    Figure 6. Plan of the typical block with available surface for the PV panels.

    5.3. PV energy yields

    The PV energy yields has been calculated through the software platform PVGIS [36]. Figure 7 shows the monthly solar radiation, deriving by the database "climate SAF-PVGIS", incident on the different facing and surfaces.

    Figure 7. Monthly global irradiation (kWh/m2).

    The yearly global radiations at the different orientation are:

    West-East façade (90°): 1,285 kWh/m2y;
    South façade (90°): 982 kWh/m2y;
    West Sloped roof (15°): 1,793 kWh/m2y;
    South Sloped roof (15°): 2,012 kWh/m2y.

    The following Table shows the available surfaces and their orientation on which to install the PV panels for each of the 39 apartments and on the staircase roof for each block.

    The usable surface has been calculated considering the number of the PV panels that can be hosted in the available surfaces and the relative installed peak power (kWp).

    The yearly electricity production Em(kWh) have been calculated through the PVGIS tool. The system energy loss has been assumed by 15.5%, for considering both shadowing effects and the degradation of the PV performance due to cell ageing.

    Table 9. Available surface and yearly electricity production by the PV plant.
    Apartment Number Gross surface per apartment Usable surface per apartment Total usable surface
    E W S E W S E W S
    1 Type A 6 11.00 16.60 - 9.90 14.85 - 59.40 89.10 -
    Type B 3 9.70 - - 8.25 - - 24.75 - -
    2 Type C 6 8.10 16.60 - 6.60 14.85 - 39.6 89.10 -
    3 Type A 6 11.00 16.60 - 9.90 14.85 - 59.40 89.10 -
    Type B 3 9.70 - - 8.25 - - 24.75 - -
    4 Type C 3 8.10 16.60 - 6.60 14.85 - 19.80 44.50 -
    Type D 3 - 23.50 9.70 - 23.10 8.25 - 69.30 24.75
    Type E 3 - 8.50 12.20 - 8.25 11.55 - 24.75 34.65
    5 Type F 3 - - 8.50 - - 6.60 - - 19.80
    Type G 3 - 8.50 10.20 - 8.25 8.25 - 24.75 24.75
    Stair case 4 - 29.20 - - 26.04 - - 105.60 -
    Roof (β = 15°) 1 - - 29.20 - - 26.04 - - 26.04
    East (90°) West (90°) South (90°) West (β = 15°) South (β = 15°)
    Total available surface (m2) 227.70 430.65 103.95 105.60 26.04
    Installed peak power (kWp) 34.0 60.0 15.0 16.0 4.0
    Energy yield (kWh) 24,475 43,239 18,908 21,286 5,986
     | Show Table
    DownLoad: CSV

    Globally the building surface occupied by BIPV is 893.94 m2, of which 762.30 m2on the building façade and 131.64 m2 on the staircase roof. The total installed peak power is 129 kWp, which provide a yearly electricity production of 113,895 kWh, almost totally satisfy the electrical energy needs (117,000 kWh) of the 39 apartments of the multi-floor building.

    Definitively, the equation 1 gives a PE less than of 17.70 or 25.50 kWh/m2y in function of the heating system adopted. However, when a Heat Pump is adopted as heating system its energy consumptions can be satisfied by the PV plant, guaranteeing almost zero energy balance.A possible strategy for further exploit the usable surface for installing renewable energy plant is the implementation of solar panels which allow the simultaneously production of electric and thermal energy, the so-called PVT panel [37].


    6. Environmental Performances of the Implementation of the Green Roof

    Green roofs are often pointed as an efficient technology that reduce solar gain, indoor and outdoor superficial temperature fluctuations, as well as indoor air temperature peaks.

    The capability of the green roof to achieve the above mentioned performance it was analyzed through the DesignBuilder Software. In particular, the internal (Tsi) and external (Tso) superficial temperatures were calculated in free running conditions (without ACs) for both a traditional roof (TR) and a green roof (GR). Figure 8 shows the trends of these temperatures during the period (15th July–15stAugust).

    Figure 8. Daily profiles of outer and inner surface temperature.

    It is possible to notice that throughout the period investigated the Tso of (TR) is always higher than Tso of (GR). The average difference between Tso(TR) and Tso(GR) is of about 7.0 ℃, with a maximum daily value of 9.50 ℃.

    The trend of Tsi(TR) keeps its profile averagely around 30 ℃ with peak values of 31 ℃ while Tsi(GR) has values almost of 26 ℃. Therefore, a significant average difference equal to 4 ℃ and a maximum daily value of 5 ℃ between the values of Tsi(TR) and Tsi(GR) have been obtained. It is important to highlight which the profile of Tsi(GR) is rather flat if compared to the Tsi(TR), this indicates which the green roof reduces the hourly fluctuations of Tsi. This is due to the soil layer which with its thermal mass and the water content it absorbs, stores and releases the heat in the nocturnal hours [38,39].


    7. Economic Analysis Results

    The above listed energy efficient measure of the building envelope and systems are now considered from the economic and financial perspectives, in order to compare the two options, new construction and retrofit, and select their optimal arrangement.

    At first, the nZEB program costs and revenues have been represented separately, showing the associated costs and revenues related to each proposed interventions: thermal insulation (1.TI), windows (2.WI), green roof (3.GR), ventilated facades (4.VF), thermal bridges (5.TB), condensing boiler (6.CB), heat pump (7.HP), solar thermal (8.ST) and mono-cristalline photovoltaic (9.PV) (Table 10).

    Table 10. Costs and revenues for each component of the nZEB program considering the cases of new building and retrofit (€).
    New building TI WI GR VF TB CB HP ST PV
    Unitary cost 17 45 51 85 239 31815 46502 554 416
    Investment cost (Stock) 48247 30034 52090 203162 58584 27915 46502 33246 336733
    Maintenance (annuity for the whole life cycle) 420 56 514 0 282 500 360 300 324
    Incentives (annuity for ten years) 0 0 0 0 0 0 0 0 16200
    Savings (annuity for the whole life cycle) 6289 1978 690 -696 2280 2915 10502 3246 14148
    Retrofit TI WI GR VF TB CB HB ST PV
    Unitary cost 70 507 51 85 - 31815 46502 554 462
    Investment cost (Stock) 196299 338704 52090 203304 - 31815 46502 33246 374148
    Maintenance (annuity for the whole life cycle) 420 654 514 0 - 500 360 300 324
    Incentives (annuity for ten years) 12351 21887 3341 13260 - 1879 2340 3900 18000
    Savings (annuity for the whole life cycle) 6289 1978 690 –696 - 2915 10502 6492 14148
     | Show Table
    DownLoad: CSV

    Table 11 shows the NPV calculated for each energy efficient measure as well as the two scenarios, considering two life cycle of 30 (medium term) and 100 years (long term). The 100-years period is just an illustrative hypothesis for testing the convenience under the perspective of the willingness to expect.

    Table 11. NPV (thousands €) for both new building and retrofit scenario in medium (30 years) and long (100 years) run.
    1.TI 2.WI 3.GR 4.VF 5.TB 6.CB 7.HP 8.ST 9.PV
    30 years New building 68 –5 –87 –239 –30 13 161 17 –85
    Retrofit –29 –294 –57 –122 - 26 181 34 –94
    100 years New building 157 14 –109 –251 –5 44 315 54 –4
    Retrofit 28 –388 –80 –134 - 56 336 71 –5
     | Show Table
    DownLoad: CSV

    The energy efficient measure 6.CB (HS1) and 7.HP (HS2) are alternative. Further the NPV of the whole energy efficient measure has been calculated for all the set of possible alternative: New building with CB (S1HS1), New building with HP (S1HS2), Retrofit with CB (S2HS1), Retrofit with HP (S2HS2).

    Table 12. Total NPV (thousands €) for both new building and retrofit scenario in medium (30 years) and long (100 years) run.
    T = 30 y T = 100 y
    S1HS1 S2HS1 S1HS2 S2HS2 S1HS1 S2HS1 S1HS2 S2HS2
    NPV –263 –443 –201 –382 –95 –444 174 –168
     | Show Table
    DownLoad: CSV

    It is possible notice that the minimum discounted payback period, even not economically significant, occurs in the new building scenario when the Heat Pump is chosen as heating system (lower left graph).

    Then, the retrofit scenario, despite the availability of government incentives, cannot compensate the highest initial cost. The consolidated discounted cash flows—annual (blue) and cumulated (red) in the long term period are displayed in Figure 9.

    Figure 9. Discount cash flows (DCF) in M€.

    Table 13 shows the other financial indices that have been calculated. Despite the general scarcity of the economic performances displayed in Table 13, some remarks can be pointed out. The new building scenario, from all the perspectives, achieve the most attractive performance, despite the government incentives that significantly support energy retrofit and renovation. Furthermore, the implementation of the heat pump system for environmental heating provides the higher performance both in new building and in retrofit scenario.

    Table 13. Economic results and financial indices.
    T = 30 y T = 100 y
    S1HS1 S2HS1 S1HS2 S2HS2 S1HS1 S2HS1 S1HS2 S2HS2
    ERR (%) –0.27 0.24 1.49 1.26 2.17 1.74 2.60 2.26
    IRR (%) –4.98 –10.91 –2.20 –3.89 –0.65 - 0.73 –0.74
    DPP (years) > 100 > 100 54 > 100 > 100 > 100 54 > 100
     | Show Table
    DownLoad: CSV

    The favourable results of the long term scenario allow us to appreciate the positive impact in terms of economic performances coming from the willingness to expect of the owners, that a situation of low inflation and low interest rates as the current one can encourage. The relevance of this result specifically concerns the environmental policy matters about the choices of the kind and the amount of the supports to implement.

    Due to the poorness of the economic results of Ventilated Facades and Green Roof both in medium and long term, the financial indices have been recalculated excluding these energy efficiency measure (Table 14).

    Table 14. Economic results and financial indices.
    T = 30 y T = 100 y
    New Building Retrofit New Building Retrofit
    NPV (k€) 139 –176 578 102
    ERR (%) 3.21 1.83 3.13 2.50
    IRR (%) 1.95 –1.96 3.44 0.49
    DPP (years) 20 60 20 60
     | Show Table
    DownLoad: CSV

    The red numbers indicate the values considered insufficient or exceeding the benchmarks. It is possible to point out the satisfying economic performances of this configuration especially in case of new building.


    8. Conclusion

    This study analyses the extra cost necessary to reach the nZEB target in the case of the energy retrofit of an existing multistore building (scenario 1) and in the case to directly realize a building with achieve the nZEB status (scenario 2). Further, the two scenarios have been compared under financial point of view.

    For obtaining a nearly zero energy balance, it is necessary to upgrade the performance of the building envelope in combination with the energy generation system in comparison to a reference building. The analysed energy efficient measure under investigated are that one commonly used in the current building design: ETICS, Efficient windows, Ventilated façade, green roof, Heat Pump and condensing boiler.

    However, only such strategy, which significantly contribute to diminish the energy demand of the building, is not sufficient to reach a nearly zero balance of the energy needs.

    Therefore, it is compulsory the local production of energy through renewable source, which allows obtaining a nearly zero energy balance.

    More specifically the implementation of a solar thermal plant of about 117 m2, which satisfy by 80% of the energy needs for the production of DHW, and about 893 m2 of PV panels, which satisfy almost totally the energy needs of both electric appliance and of the Heat Pump.

    From these results, one can point outs the enormous requirements of available surfaces, more than 1000 m2, where install the solar panels that can be satisfied only by exploiting the BIPV technology.

    The implementation of the same energy efficient measure involves different cost for the two scenarios. Indeed, in the case of the refurbishment of an existing building extra costs are necessary for provisional scaffolders and to demolish the pre-existent components of the building envelope that needs to be upgraded.

    The financial analysis shows that some of the energy efficient measures implemented for upgrading the building envelope are less cost-effective, (i.e. ventilated façade and green roof) in comparison with the upgrade of the energy generation system.

    However, the implementation of a ventilated façade and of a green roof allows to obtain some other specific benefits that are not directly monetizable (aesthetic value, improve of the microclimate).

    The economic-financial analysis confirmed the clear preferability of the first scenario, (i.e. new building) option envisaging sustainable constructive technologies, heat pump (HS2) and solar thermal system by most of the points of view.

    The long-term strategy highlights the possibility to achieve positive financial indices thanks to the significantly cheaper environmental investments. Therefore, high initial costs and long payback periods, financial barriers, are the main obstacles for increase the spreading of the nZEB.


    Conflict of Interest

    All authors declare no conflicts of interest in this paper.


    [1] European Commission, Directive 2010/31/EU on the energy performance of buildings (recast), 2010. Available from: https://ec.europa.eu/energy/en/topics/energy.../buildings.
    [2] Ramesh T, Prakash R, Shukla KK (2010) Life cycle energy analysis of buildings: an overview. Energ Buildings 42: 1592–1600. doi: 10.1016/j.enbuild.2010.05.007
    [3] Hamdy M, Hasan A, Siren H (2013) A multi-stage optimization method for cost-optimal and nearly-zero-energy building solutions in line with the EPBD-recast 2010. Energ Buildings 56: 189–203. doi: 10.1016/j.enbuild.2012.08.023
    [4] Georges L, Massart C, Moeseke G, et al. (2012) Environmental and economic performance of heating systems for energy-efficient dwellings: case of passive and low-energy single-family houses. Energ Policy 40: 452–464. doi: 10.1016/j.enpol.2011.10.037
    [5] Marszal AJ, Heiselberg P (2011) Life cycle cost analysis of a multi-storey residential net zero energy building in Denmark. Energy 41: 5600–5609.
    [6] Wang L, Gwilliam J, Jones P (2009) Case study of zero energy house design in UK. Energ Buildings 41: 1215–1222. doi: 10.1016/j.enbuild.2009.07.001
    [7] Gagliano A, Patania F, Capizzi A et al. (2012) A proposed methodology for estimating the performance of small wind turbines in urban area. Sustain Energ Buildings 12: 539–548. doi: 10.1007/978-3-642-27509-8_45
    [8] Gagliano A, Patania F, Nocera F, et al. (2013) GIS-based decision support for solar photovoltaic planning in urban environment. Sustain Energ Buildings 22: 865–874. doi: 10.1007/978-3-642-36645-1_77
    [9] Net Zeb evaluation tool, User guide, 2012. Available from: http://task40.iea-shc.org/Data/Sites/11/documents/net-zeb/Net-ZEB-Evaluation-Tool-User-Guide.pdf.
    [10] Salom J, Widén J, Candanedo J, et al. (2011) Understanding net zero energy buildings: evaluation of load matching and grid interaction indicators. In: Proceedings of Building Simulations, Sidney.
    [11] Satori I, Napolitano A, Marszal A, et al. (2012) Criteria for definition of net zero energy buildings. Available from: http://www.iea-shc.org/publications/task.aspx?Task¼40.
    [12] Goggins J, Moran P, Armstrong A, et al. (2016) Lifecycle environmental and economic performance of nearly zero energy buildings (NZEB) in Ireland. Energ Buildings 116: 622–637. doi: 10.1016/j.enbuild.2016.01.016
    [13] Krati M, Ihm P (2016) Evaluation of net-zero energy residential buildings in the MENA region. Sustain Cities Soc 22: 116–125. doi: 10.1016/j.scs.2016.02.007
    [14] Brinks P, Kornadt O, Oly R (2016) Development of concepts for cost-optimal nearly zero-energy buildings for the industrial steel building sector. Appl Energ 173: 343–354. doi: 10.1016/j.apenergy.2016.04.007
    [15] Kristjansdottir TF, Good CS, Inman MR, et al. (2016) Embodied greenhouse gas emissions from PV systems in Norwegian residential zero emission pilot buildings. Sol Energy 133: 155–171. doi: 10.1016/j.solener.2016.03.063
    [16] Chastas P, Theodosiou T, Bikas T (2016) Embodied energy in residential buildings-towards the nearly zero energy building: a literature review. Build Environ 105: 267–282. doi: 10.1016/j.buildenv.2016.05.040
    [17] Kolokotsa D, Rovas D, Kosmatopoulos E, et al. (2011) A roadmap towards intelligent net zero- and positive-energy buildings. Sol Energy 85: 3067–3084.
    [18] Cho S, Lee JS, Jang JY (2008) Development of integrated operation, low-end energy building engineering technology in Korea. In: EKC2008 Proceedings of the EU-KOREA Conference on Science and Technology, Springer Proceedings in Physics, 123–133.
    [19] Barthelmes VM, Becchio C, Corgnati SP, et al. (2015) Replicability of nZEBs on real estate market in mediterranean countries. Energ Procedia 82: 452–457. doi: 10.1016/j.egypro.2015.11.843
    [20] Giuffrida S, Ferluga G, Valenti A (2015) Capitalization rates and 'real estate semantic chains': an application of clustering analysis. Int J Business Intelligence Data Mining 10(2). Available from: http://dx.doi.org/10.1504/IJBIDM. 2015.069271.
    [21] Napoli G (2015) Financial sustainability and morphogenesis of urban transformation projects. In: Gervasi O et al., ICCSA 2015, Part III LNCS, Switzerland: Springer International Publishing, 178–193. Available from: doi:10.1007/978-3-319-21470-2.
    [22] MasterClima Aermec. Available from: http://www.masterclima.info/.
    [23] Design Builder-energy simulation software, version 3. Available from: http://designbuilder.co.uk.
    [24] Bottarelli M, Gabrielli L (2011) Payback period for a ground source heat pump system. Int J Heat Tech 29: 145–150.
    [25] Sullivan WG, Wicks EM, Luxhoj JT (2006) Engineering Economy, In: 13 th Eds., New Jersey: Pearson Prentice Hall, 212–213.
    [26] Mancarella P, Canova A, Chicco G, et al. (2009) Cogenerazione distribuita a gas naturale. Modelli e tecniche per valutazioni energetiche ambientali ed economiche, Milano: Franco Angeli.
    [27] Simonotti M (1997) La stima immobiliare con principi di economia e applicazioni estimative, Milano: UTET Libreria.
    [28] UNI EN ISO 10077-1 (2006) Thermal performance of windows, doors and shutters-Calculation of thermal transmittance-Numerical method for frame.
    [29] UNI EN 673-2005, Glass in building-Determination of Thermal transmittance-Calculation method.
    [30] UNI EN ISO 6946 Elements and components in buildings-Thermal resistance and transmittance -Calculation method.
    [31] UNI EN ISO 13786:2008 Thermal Performance of Building Components-Dynamic Thermal Characteristics-Calculation Methods.
    [32] European Commission, Commission Delegated Regulation (Eu) No 244/2012, Available from: www.buildup.eu › Practices › Publications.
    [33] Enea, Solterm, Solar Calculator. Available from: http://www.solaritaly.enea.it/CalcRggmmNorm/Calcola1.php.
    [34] Duffie JA, Beckman WA (1991) Solar Engineering of Thermal Processes. John Wiley & Sons.
    [35] TERNA, Dati statistici sugli impianti e la produzione di energia elettrica in Italia, 2007. Available from: www.terna.it.
    [36] Joint Research Centre, Photovoltaic Geographical Information System (PVGIS), Available from: http://re.jrc.ec.europa.eu/pvgis/apps4/pvest.php.
    [37] Tina G, Cosentino F, Notton G (2012) Effect of thermal gradient on electrical efficiency of hybrid PV/T. In: 25th European photovoltaic solar energy conference and exhibition, Valencia, Spain.
    [38] Susca T, Gaffin SR, Dell'Osso GR (2011) Positive effects of vegetation: Urban heat island and green roofs. Environ Pollut 159: 2119–2126. doi: 10.1016/j.envpol.2011.03.007
    [39] Gagliano A, Detommaso M, Nocera F, et al. (2014) The retrofit of existing buildings through the exploitation of the green roofs-a simulation study. Energy Procedia 62: 52–61. doi: 10.1016/j.egypro.2014.12.366
  • This article has been cited by:

    1. Salvatore Giuffrida, Vittoria Ventura, Francesco Nocera, Maria Rosa Trovato, Filippo Gagliano, 2020, Chapter 24, 978-3-030-23784-4, 425, 10.1007/978-3-030-23786-8_24
    2. A. Gagliano, S. Aneli, Analysis of the energy performance of an Opaque Ventilated Façade under winter and summer weather conditions, 2020, 205, 0038092X, 531, 10.1016/j.solener.2020.05.078
    3. Maria Rosa Trovato, Francesco Nocera, Salvatore Giuffrida, Life-Cycle Assessment and Monetary Measurements for the Carbon Footprint Reduction of Public Buildings, 2020, 12, 2071-1050, 3460, 10.3390/su12083460
    4. Anna Życzyńska, Dariusz Majerek, Zbigniew Suchorab, Agnieszka Żelazna, Václav Kočí, Robert Černý, Improving the Energy Performance of Public Buildings Equipped with Individual Gas Boilers Due to Thermal Retrofitting, 2021, 14, 1996-1073, 1565, 10.3390/en14061565
    5. Grazia Napoli, Marta Bottero, Giuseppina Ciulla, Federico Dell’Anna, José Rui Figueira, Salvatore Greco, Supporting public decision process in buildings energy retrofitting operations: The application of a Multiple Criteria Decision Aiding model to a case study in Southern Italy, 2020, 60, 22106707, 102214, 10.1016/j.scs.2020.102214
    6. Maurizio Detommaso, Antonio Gagliano, Luigi Marletta, Francesco Nocera, Fabio Bisegna, Lamberto Tronchin, 2020, Effectiveness of VIPs and PCMs on the energy performance and thermal comfort in buildings, 978-1-7281-7455-6, 1, 10.1109/EEEIC/ICPSEurope49358.2020.9160717
    7. Grazia Napoli, Simona Barbaro, Salvatore Giuffrida, Maria Rosa Trovato, 2021, Chapter 116, 978-3-030-48278-7, 1248, 10.1007/978-3-030-48279-4_116
    8. Francesco Nocera, Salvatore Giuffrida, Maria Rosa Trovato, Antonio Gagliano, Energy and New Economic Approach for Nearly Zero Energy Hotels, 2019, 21, 1099-4300, 639, 10.3390/e21070639
    9. A. Carratt, G. Kokogiannakis, D. Daly, A critical review of methods for the performance evaluation of passive thermal retrofits in residential buildings, 2020, 263, 09596526, 121408, 10.1016/j.jclepro.2020.121408
    10. Grazia Napoli, Antonella Mamì, Simona Barbaro, Serena Lupo, 2020, Chapter 6, 978-3-030-23784-4, 89, 10.1007/978-3-030-23786-8_6
    11. Simona Barbaro, Grazia Napoli, 2021, Chapter 7, 978-3-030-86978-6, 93, 10.1007/978-3-030-86979-3_7
    12. Maria Rosa Trovato, Cheren Cappello, Climate Adaptation Heuristic Planning Support System (HPSS): Green-Blue Strategies to Support the Ecological Transition of Historic Centres, 2022, 11, 2073-445X, 773, 10.3390/land11060773
    13. Pablo Olasolo-Alonso, Luis M. López-Ochoa, Jesús Las-Heras-Casas, Luis M. López-González, Energy Performance of Buildings Directive implementation in Southern European countries: A review, 2023, 281, 03787788, 112751, 10.1016/j.enbuild.2022.112751
    14. Dayane Cynthia Pinto Oliveira, Max Chianca Pimentel Filho, Antonio Alisson Alencar Freitas, 2021, Energy efficiency diagnosis and improvements for electrical systems in Brazilian university buildings using RTQ-C regulation, 978-1-6654-2928-3, 359, 10.1109/EPEC52095.2021.9621587
    15. Federico Dell’Anna, Carlos Marmolejo-Duarte, Marina Bravi, Marta Bottero, A choice experiment for testing the energy-efficiency mortgage as a tool for promoting sustainable finance, 2022, 15, 1570-646X, 10.1007/s12053-022-10035-y
    16. Individual Re-Identification in Blurred Image using SVM/PCA Technique, 2022, 2581-9429, 261, 10.48175/IJARSCT-4594
    17. Martina Bertoncini, Adele Boggio, Federico Dell'Anna, Cristina Becchio, Marta Bottero, An application of the PROMETHEE II method for the comparison of energy requalification strategies to design Post-Carbon Cities, 2022, 10, 2333-8334, 553, 10.3934/energy.2022028
    18. Milica Vujovic, Djordje Stojanovic, Tina Selami, Michael Hensel, Design and science: Content analysis of published peer-reviewed research over the last four decades, 2023, 20952635, 10.1016/j.foar.2023.04.001
    19. Simona Barbaro, Grazia Napoli, Energy Communities in Urban Areas: Comparison of Energy Strategy and Economic Feasibility in Italy and Spain, 2023, 12, 2073-445X, 1282, 10.3390/land12071282
    20. Simona Barbaro, Grazia Napoli, Towards a participatory energy transition. Critical issues and potentials of regulatory and financial instruments for Renewable Energy Communities (RECs) in Italy, 2024, 35, 2036-2404, 69, 10.48264/VVSIEV-20243506
  • Reader Comments
  • © 2017 the Author(s), licensee AIMS Press. This is an open access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0)
通讯作者: 陈斌, bchen63@163.com
  • 1. 

    沈阳化工大学材料科学与工程学院 沈阳 110142

  1. 本站搜索
  2. 百度学术搜索
  3. 万方数据库搜索
  4. CNKI搜索

Metrics

Article views(6349) PDF downloads(1114) Cited by(20)

Article outline

Figures and Tables

Figures(9)  /  Tables(14)

/

DownLoad:  Full-Size Img  PowerPoint
Return
Return

Catalog